Fireproof paste A (10 kg)
Flame Cabel A Paste os a single-component, non-flammable ablation paste, which is an aqueous dispersion of synthetic resin. Any coating made of this material is completely resistant to fire. It is charakterized by its endothermic properties. Om case of fire, it stops the propgation by relasing large quantities of water.
Technical documentation
Separate crossing
Mixed crossing
TECHNICAL DATA:
- Fire resistance class: up to EI 120
- Colour: creamy
- Environmental class: Z1,Z2
- Density: 1.56 ± 5% g/cm³
- Non volatile content, %: 79.0 ± 5%
- Storage temperature range: from +5°C to +30°C
- Shelf life, no limit to application: 10 months in oryginally sealed container
- Theoretical paint amount (kg / m²) needed to obtain 1mm thick coating: 1,93 kg/m²
- Commercial package: 10 kg
- Oxygen index: ≥45 (i.e. completly non-flammable product)
- Technical Approval: AT-15-7807/2016, ETA-15/0853 (expansion joints)
- Cert. of conformity: ITB-2404/W
- Hygienic Certyficate: HK/B/0557/01/2014
- Declaration od Confirmity: CARBO/002-07-01-2016
APPLICATION:
The way of protecting flammable pipes with mineral wool cover.
- Step 1: Put Multitube on the pipe under the insulation and slide it into the wall.Then put insulation on the pipe and a tape.
- Step 2: Fill the remaining space with mineral wool. By using a putty knife, apply Flame Cabel Pasta A to form a ring with a width of min. 50 mm and thickness min. 0.6 mm.
- Step 3: Apply Flame Cabel Pasta A to the pipe cover so that a ring forms with a width of min. 50 mm and thickness min. 0.6 mm.
- Step 4: Mark the penetration with the attached label, mark Flame Cabel Pasta A and Multitube on it, enter the date and name.
PENETRATIONS
- Clean the penetration opening, cables and pipes. Degrease, if required.
- Install the mineral wool boards.
- Protect the adjoing surfaces with a tape.
- Mix the flame Cabel A Paste.
- Apply several layers with a spatula.
- Mark the penetration seal with the information imprint supplied together with each bucket of the Flam Cabel A Paste.
LINEAR JOINTS
- Clean the joint.
- Protect the adjoining surfaces with a tape.
- Mix the Flame Cabel A Paste.
- Insert mineral wool into the joint.
- Apply the required amont of the paste with a spatula.
- Mark the made penetration seal with the information imprint supplied together with each bucket of the Flame Cabel A Paste.
Related services categories
In your cart
Sale
Useful information
Dear Customers!
The stock and the price of the product are for information only and may change during the day.
For an exact price offer, please contact us
+371 67249249 or sales@latakva.com