Brandsäkra väggar och skiljeväggar

Brandklassad vägg Tecbor® A 12 EI-240 väggfoder på keramisk murverk

Solution

  1. Tecbor® A 12 mm boards.
  2. 15x45x0,5 mm omega sections.
  3. 10x60 mm anchor.
  4. Tecbor® joint pasta.
  5. 3,5x25 mm self-drilling screw.
  6. ≥ 12,3 cm ceramic brick wall.
  7. 10 mm plastering.

Test

  • Standard :UNE EN 1364-1
  • Laboratory :APPLUS
  • Test Nº :07/32302900

Non-structural walls, which separate fire areas, should be fire resistant as stipulated in standard EN 1364-1.

When in Brandtålighet tests for non-structural elements one edge is left free (Part 1: Walls), the standard allows increasing the width.

With regard to increasing the Höjd, the standard is clear and precise. When the test is run at least at 3 metres high, it may be increased up to 4 metres.

Very often, internal partitions are higher than 4 metres. mercor tecresa® have been the first to develop large partitions and offers the most efficient and convenient solution for this typ of works.

Besides, penetrations produced between different fire sectors must be sealed off; for example, in the case of services crossing. Check the Tecsel® Sealing System catalogue to find the most suitable solution.

Description of assembly

  • On a 12 cm ceramic brick wall with 10 mm plastering on the unexposed side, attach 15x45x0.5 mm omega metal profiles every 610 mm using 10x60 mm anchors. Then fix Tecbor® A 12 mm boards with 3.5x25 mm self-drilling screws.
  • Use Tecbor® joint pasta in screw heads and between boards.
  • Distance between screws should be 250-300 mm cirka.